Skip to main content

TESTING OF BUSHINGS

POWER FREQUENCY TESTS

POWER FACTOR–VOLTAGE TEST:

  • In this test, bushing is set up as in service or immersed in oil.
  • It is connected such that the line conductor goes to the high-voltage side and the tank or earth portion goes to the detector side of the high-voltage Schering-bridge.
  • Voltage is applied up to the line value varied in steps and then reduced.
  • The capacitance and power factor (or tan δ) are recorded at each step and their characteristics are drawn.
  • This is a normal routine test but sometimes may be conducted on percentage basis.

INTERNAL OR PARTIAL DISCHARGE TEST

This test is used to find the deterioration or failure due to internal discharges caused in the composite insulation of the bushing.

  • The voltage versus discharge magnitude as well as the quadratic rate, gives an excellent record of the performance of the bushing in service.
  • This is a routine test for high-voltage bushings.

MOMENTARY WITHSTAND TEST AT POWER FREQUENCY:

This is done as per the Indian Standard Specifications, IS: 2099, applied to bushings.

  • The bushing has to withstand without flashover or puncture for a minimum time( ~ 30 s) to measure the voltage.
  • Presently this test is replaced by the impulse withstand test.

ONE MINUTE WET WITHSTAND TEST AT POWER FREQUENCY

Common and routine tests used for all electrical apparatuses are the one-minute wet, and dry voltage withstand tests.

  • In wet test, voltage specified is applied to the bushing mounted as in service with the rain arrangement.
  • A properly designed bushing has to withstand the voltage without flashover for one minute.

VISIBLE DISCHARGE TEST AT POWER FREQUENCY:

This test is used for determining whether the bushing is likely to give radio interference in service, when the voltage specified in IS: 2009 is applied.

  • No discharge other than that from the arcing horns or grading rings should be visible to the observers in a dark room.
  • The test arrangement is the same as that of the withstand test, but the test is conducted in a dark room.

Comments

Popular posts from this blog

LOSS OF CHARGE METHOD

 Current-time characteristic of the discharge current is obtained by placing the switch B in position 2. The slope of these current time characteristic gives the time constant τ = CR, where      C is the capacitance of the specimen. The volume resistance of the specimen R can thus be obtained from the relationship by measuring τ and C. Alternatively, a capacitance previously charged (C1) may be discharged through the specimen by inserting it in place of the battery E. By knowing the value of the capacitance C1 which is very large compared to the specimen capacitance (≈10 μF) and knowing the current-time characteristic of the discharge current, its time constant can be calculated. Hence, the resistance of the specimen is obtained from the relationship        𝑅=𝜏/𝐶1 where C1 – capacitance used τ – time constant. If initial voltage V0 on the capacitor is measured and the voltage V across it at any time τ Then the unknown resistance R can be calcul...

PARTIAL DISCHARGE REPRESENTATION:

                          The weak points in an insulation like voids, cracks, and other imperfections lead to internal or discharges in the insulation and as they are small, were not revealed in capacitance measurements but revealed as power loss components, contributing for an increase in the dissipation factor                                 ‘PARTIAL DISCHARGES’ in a course of time reduces the strength of insulation leading to a total or partial failure or breakdown of the insulation Consider           Ca as capacitor with a void inside the insulation. Capacitance of the void is represented by a capacitor in series with the rest of the insulation capacitance (Cb). The remaining void-free material is represented by the capacitance Cc When the voltage across the capacitor is raised, a critical value is reached acr...